Figure: 30 TAC §290.47(f)

The following form must be completed for each assembly tested. A signed and dated original must be submitted
to the public water supplier for recordkeeping purposes:

BACKFLOW PREVENTION ASSEMBLY TEST AND MAINTENANCE REPORT

NAME OF PWS: ______________________________________________________________
PWS I.D.: #___________________________________________________________________
MAILING ADDRESS: __________________________________________________________
CONTACT PERSON: __________________________________________________________
LOCATION OF SERVICE: ______________________________________________________

The backflow prevention assembly detailed below has been tested and maintained as required by commission
regulations and is certified to be operating within acceptable parameters.

TYPE OF ASSEMBLY

           ¨ Reduced Pressure Principle                                 ¨ Reduced Pressure Principle-Detector
           ¨ Double Check Valve                                           ¨ Double Check-Detector
           ¨ Pressure Vacuum Breaker                                   ¨ Spill-Resistant Pressure Vacuum Breaker

Manufacturer____________________           Size _________________________________
Model Number__________________           Located At ___________________________
Serial Number_____________________________________________________________

Is the assembly installed in accordance with manufacturer recommendations and/or local codes?______

 

Reduced Pressure Principle Assembly

Pressure Vacuum Breaker

 

Double Check Valve Assembly

 

Air Inlet

Check Valve

 

1st Check

2nd Check

Relief Valve

Initial Test

Held at ____ psid
Closed Tight
  ¨
Leaked
         ¨

Held at ____ psid
Closed Tight
  ¨
Leaked
          ¨

Opened at ___ psid
Did not open
      ¨

Opened at ____ psid
Did not open
    ¨

Held at _____ psid
Leaked
        ¨

Repairs and Materials Used

 

 

 

 

 

Test After Repair

Held at ____ psid
Closed Tight
  ¨

Held at ____ psid
Closed Tight
  ¨

Opened at ___ psid

Opened at ____ psid

Held at _____ psid

Test gauge used: Make/Model___________ SN:_____________ Calibration Date:___________
Remarks:______________________________________________________________________
The above is certified to be true at the time of testing.
Firm Name ________________________ Certified Tester ______________________
Firm Address ______________________ Cert. Tester No. __________ Date_______
Firm Phone #______________________

* TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS
** USE ONLY MANUFACTURER'S REPLACEMENT PARTS